Preventive maintenance contracts

Most emergency calls we take were preventable, and cheaply. A fouled condenser and a failed door gasket do not announce themselves. They quietly raise head pressure and run hours up until a compressor gives out on the busiest night of the year.

Answered live, 24/7 (617) 938-5404
Request a callbackor call (617) 938-5404, answered live 24/7

What a real PM visit includes

A maintenance visit that is just a look and a signature is worth nothing. Here is the actual task list and why each item is on it.

IntervalTaskWhy it is on the list
Monthly, greasy kitchensCondenser chemical clean, fan bearing inspectionKitchen exhaust grease binds to coil fins and is the single most common cause of high head pressure
QuarterlyHead pressure trended against ambientCatches slow degradation months before it is a failure. One reading tells you nothing; four tell you everything
SemiannualDoor gaskets, defrost heaters, TXV bulb security and insulationA loose or uninsulated TXV bulb causes floodback that looks like a dozen other faults
SemiannualEvaporator, compressor and condenser inspectionThe three places failures actually originate
AnnualDrier replacement if opened, capacitor testing, full electrical auditCapacitors fail gradually. Replace below 10% of rated microfarads, before the motor overheats
Every visitDrain pan and line clear, slope verified, freezer drain heater confirmedA refrozen drain line backs water onto the coil. It is the classic New England winter callback
Every visitThermometer calibration, temperature log checkMassachusetts requires unit thermometers accurate to ±3°F and food probes to ±2°F

Coil cleaning is done with brush, vacuum, water or a proper coil foam, never acid-based foam. It attacks the fins and the tube, and it buys you a clean-looking coil now in exchange for a leak later.

Refrigerant compliance, handled as part of the contract

If any of your systems hold 50 lbs of refrigerant or more, you have obligations under 40 CFR 82.157 whether or not anyone has mentioned them. Commercial refrigeration carries a 20% annual leak rate trigger. Repairs are due within 30 days of discovery, with a verification test after, and a follow-up verification within 10 days of that. Records are kept three years. A system leaking 125% or more of its full charge in a calendar year has to be reported to the EPA.

Contract customers get that tracking as part of the visit rather than as a panic exercise when somebody asks for the file.

The refrigerant transition, and what it means for your planning

There has been a lot of noise about equipment deadlines. The current position, after the EPA amended the AIM Act Technology Transitions rule in May 2026, is more relaxed than most published advice still says. Supermarket refrigeration systems now sit under an interim 1,400 GWP limit and cold storage warehouses under 700, both until 1 January 2032. Refrigerated lab equipment moved to 2028, industrial process refrigeration to 2030.

In plain terms: the large installed base of older equipment across Greater Boston is serviceable for years yet, and you are not being forced into a capital replacement this year. What has changed is the replacement decision when a unit does die, 310 CMR 7.76 names R-404A among prohibited substances for new equipment in Massachusetts, so like-for-like is closed off even though your existing unit is grandfathered and can keep running.

What it costs and how it is priced

Priced per unit, on a quarterly or monthly schedule depending on the equipment and the environment it lives in. A single reach-in in a quiet dining room and a rack of walk-ins behind a wood-fired grill are not the same maintenance problem and should not be the same price. Contract customers get priority dispatch when something does fail, and a documented service history, which matters more than most operators expect the first time an inspector asks for it.

Common questions

How often should a commercial condenser be cleaned?
Quarterly is a reasonable baseline. Monthly if the unit is anywhere near kitchen exhaust, because grease binds to the fins and does not blow off. If you can see the coil is furred, it has been costing you compressor hours and electricity for a while already.
Will a maintenance contract actually save money?
It depends how much your equipment costs you when it fails, not how much the visit costs. If a failed walk-in means a weekend of lost prep and a truck at overtime, prevention pays quickly. If you have one reach-in and a spare, it may not. We would rather tell you that than sell you a plan you do not need.
Do you provide temperature logs for inspections?
Yes. Digital temperature and service records are part of the contract, and we verify that any logging you already have is actually recording rather than just displaying. Massachusetts inspectors can ask for logs, and “the screen said 38” is not a record.
Do I have to use you for repairs too?
No. Contract customers get priority dispatch and their diagnostic history is already on file, which makes repairs faster and usually cheaper. But the maintenance contract is not a lock-in.

Related

Want a maintenance quote?

Tell us what equipment you run and where, and we price it per unit. No lock-in, no bundled extras.

(617) 938-5404

Get in touch

Request service or a quote

If something is down right now, call. The phone is the fast path, day or night. For quotes, maintenance plans and installs, send the form.

Emergency line, answered live (617) 938-5404 24 hours a day, every day of the year
Quotes, maintenance plans, installs Send the form Someone gets back to you the same day. Certificate of insurance available on request.
Accounts Purchase orders & net 30 Available for established commercial accounts

If it is down right now, calling is faster. The line is answered live at any hour.